Level 3 · The barrier counter
Wall power and circuit check
Add up the DC loads fed by one power supply, turn that into watts at the wall and amps on the circuit, and compare the amps with 80 percent of the breaker rating, a screening threshold for a load that runs for 3 hours or more. Every figure here is an estimate from the numbers you type, and nothing is pre-filled.
Barrier counter (estimate)
Enter the power of at least one component, in watts.
- DC load
- –
- Wall power
- –
- Current (at the entered power factor)
- –
- Screening threshold (80% of breaker)
- –
- Share of breaker
- Wall watts to the threshold
- –
The gauge is drawn up to 125 percent of the breaker rating and stops there.
The formulas
- Wall power (W) = DC load (W) ÷ (efficiency ÷ 100)
- Current (A) = wall power (W) ÷ (voltage (V, RMS) × power factor)
- Screening threshold (A) = 0.8 × breaker rating (A)
- Share of breaker (%) = 100 × current (A) ÷ breaker rating (A)
- Wall watts to the threshold (W) = threshold (A) × voltage (V) × power factor − wall power (W), at the power factor you entered
The power factor is the true power factor of the supply (real power divided by RMS volts times RMS amps), so the current is the wall watts divided by volts times power factor. Efficiency is DC output divided by AC input, so wall watts are the DC load divided by the efficiency as a fraction. Both ideas are explained in the sources below.
What the 80 percent figure is
In the US National Electrical Code (NFPA 70), section 210.20(A), a branch-circuit breaker must be rated for the non-continuous load plus 125 percent of the continuous load. A continuous load is one whose maximum current is expected to continue for 3 hours or more. If every load on the circuit is continuous, that works out to 0.8 × the breaker rating, which is the number this page uses. It is a screening threshold for a standard-rated breaker, not a prediction of when a breaker will trip.
Mixed loads (some continuous, some not) are calculated differently. There is an exception for assemblies listed for continuous operation at 100 percent of their rating, including the protective device. Which edition of the code applies, and any local amendments, depend on your jurisdiction, so an electrician should confirm what applies to your wiring.
Assumptions and limits
- One single-phase circuit, with the voltage you enter treated as RMS. Three-phase supplies and power distribution units need a different calculation.
- The rows are DC loads downstream of one power supply. Monitors, switches and other machines with their own supplies are separate loads on the breaker: assess and add them separately, because this tool does not include them.
- The efficiency you enter applies at this load. A supply's efficiency changes with how hard it is working, so use the figure for the nearest load point on its datasheet.
- Power factor is required. A power factor of 1 is the lowest current a given wall wattage can draw, so when you enter exactly 1 the tool shows a minimum-current scenario with no verdict. A power factor below 1 raises the current.
- The component figures are maximum draws. Short spikes above a card's rated power are not modelled.
- The 80 percent figure is the US all-continuous screening threshold described above. Other countries set their own rules.
- Calculator limits, not rules from any code: up to 24 rows, 100,000 W in total, efficiency 1 to 100 percent, voltage 1 to 1,000 V, breaker 1 to 1,000 A, power factor 0.01 to 1. The gauge is drawn to 125 percent of the breaker rating and stops there.
Sources
- NEC Information of Note, North America Standards Reference (Schneider Electric): the section 210.20(A) rule and its listed-assembly exception.
- Circuit breaker ratings explained: 80% vs 100%-rated breakers (Schneider Electric Blog, 2014): the 3-hour definition of a continuous load. It cites the 2011 edition of the NEC, so check the current edition.
- PSU: Efficiency Ratings Explained (Corsair help centre): efficiency as DC output over AC input.
- Power Factor: What it is and How to Calculate it (Fluke): power factor and current.
- NFPA 70, National Electrical Code: standard development page (National Fire Protection Association): background on the code and its editions. It does not display section 210.20(A).